Technical Specifications
Hazardous Location Classifications
UL 844:
Electric lighting fixtures for use in hazardous (classified) locationsUL 1598:
Electric lighting fixtures for use in non-hazardous locationsHazardous Location Classifications:
Class I: A hazardous location in which flammable gases or vapors may be present in the air in sufficient quantities to be explosive or ignitable, such as petroleum refineries, aircraft hangars, dry cleaning plants, utility gas plants or storage areas for liquified petroleum or natural gas, and spray finishing areas.
Division 2: Abnormal condition, where igniteable concentrations of flammable gases, vapors or liquids are not like to exist under normal operating conditions, for example:
Closed storage drums containing flammable liquids in an inside storage room would not normall allow the hazardous vapors to escape into the atmosphere. But if one of the containers is leaking, you've got an abnormal condition.
Groups A - D: The gases and vapors of Class 1 locations are broken into four groups by the Code: A,B,C, and D. These materials are grouped according to the ignition temperature of the substance, its explosion pressure, and other flammable characteristics.
Group A - The only substance in group A is acetylene because it is a gas with extremely high explosion pressures.
Group B - This group includes hydrogen and other materials with similar characteristics.
Group C & D - The most usual Class 1 groups. They comprise the greatest percentage of all Class I hazardous locations. Found in Group C is ethylene. Found in Group D are many of the most common flammable substances such as butane, gasoline, natural gas and propane.T Ratings:
HAZBAYLED™ model is T3A ratedListings
UL Listing:
Suitable for wet locations with 3/4" pendant stem Covered ceiling mount onlyIESNA LM-79 & LM-80 Testing:
RAB LED luminaires and LED components have been tested by an independent laboratory in accordance with IESNA LM-79 and LM-80.LED Characteristics
LEDs:
Three multi-chip, 26W high-output, long-life LEDsLifespan:
100,000-hour LED lifespan based on IES LM-80 results and TM-21 calculationsColor Consistency:
7-step MacAdam Ellipse binning to achieve consistent fixture-to-fixture color Color Stability:
LED color temperature is warrantied to shift no more than 200K in CCT over a 5 year periodColor Uniformity:
RAB's range of CCT (Correlated Color Temperature) follows the guidelines of the American National Standard for Specifications for the Chromaticity of Solid State Lighting (SSL) Products, ANSI C78.377.2011.Electrical
Drivers (3):
Constant Current, 720mA, Class 2 with 6kV surge protection, 100-277VAC, 50/60 HzTHD:
11.5% at 120V, 12.3% at 277VPower Factor:
98.8% at 120V, 91% at 277VConstruction
Ambient Temperature:
Suitable for 40°C (104°F) ambient temperatures.
Suitable for use in 55°C (131°F) ambient temperatures.Thermal Management:
Superior thermal management with external air-flow finsHousing:
Precision die-cast aluminum housing and door frameMounting:
Pendant mount only with 3/4" NPS pipe (pendant by others) Recommended Mounting Height:
25 ft
Lens:
Tempered glass
Reflector:
Specular vacuum metallized polycarbonate
Gaskets:
High-temperature silicone
Finish:
Formulated for high-durability and long lasting color
Green Technology:
Mercury and UV-free. RoHS compliant components. Polyester powder coat finish formulated without the use of VOCs or toxic heavy metals.
Other
Patents:
The design of the BAYLED™ is protected by patents pending in US, Canada, China, Taiwan and Mexico
Accessories:
Available accessories include protective polyshield and wire guards, replacement lens and doorframe, and an occupancy sensor.
Click here to see all accessories.Equivalency:
Equivalent to 4 lamp T8 fixtures